Control from two locations is a self-holding circuit with two start buttons and two stop buttons. The same principle also works from three or more locations.
The rule
- Stop buttons in series. Any one of them breaks the circuit and stops the motor.
- Start buttons in parallel. They are wired in parallel with the holding contact, and any one of them energises the contactor.
More control locations
A new control location is added the same way: its stop button in series with the other stop buttons, and its start button in parallel.
Common mistakes
- The stop buttons are wired in parallel. Then neither of them stops the motor on its own, because the current flows through the other one.
- The start buttons are wired in series. Then the motor starts only when both are pressed at the same time.