Self-holding circuit

A self-holding circuit keeps the contactor on after the start button is released. How to wire the start and stop buttons, the holding contact and the run light.

LNS01112S11314K11314K1A1A2K12324H1
S0 stop (NC 11–12), S1 start (NO 13–14), holding contact 13–14 of K1 in parallel with S1, and run light H1 through contact 23–24 of K1.

How it works

LNS0S1K1K1K1H11At rest

Stop button S0 is an NC contact, so voltage passes through it. S1 and the holding contact of K1 are open, and the coil is de-energised.

LNS0S1K1K1K1H12Start pressed

S1 closes and K1 energises. K1's own contact 13–14 in parallel with S1 closes, and run light H1 comes on.

LNS0S1K1K1K1H13Start released

S1 opens, but the coil is still supplied through the holding contact. K1 stays on.

LNS0S1K1K1K1H14Stop pressed

S0 opens and breaks the whole control circuit. K1 de-energises and the holding contact opens, so the motor does not start again when S0 is released.

The self-holding circuit, also called a latching or seal-in circuit, is the basic circuit of motor control. A short press switches the contactor on, and it stays on until the stop button is pressed.

Power cut

When the control voltage is lost, the contactor de-energises and the self-holding is released. When the power comes back, the motor does not start by itself. It has to be started again with the start button.

Stop has priority

When S0 is placed before the branch, stop always has priority: if both buttons are pressed at the same time, K1 does not energise. This is how motor controls are normally built. If S0 is wired in series with the holding contact only, start has priority.

Common mistakes

  • The holding contact is also wired in parallel with S0. Then the stop button does not stop the motor.
  • An NO contact is used as the stop button. NC contacts are 11–12 and 21–22, NO contacts 13–14 and 23–24.
  • A contact of another contactor is used as the holding contact. The holding must come from a contact of the same contactor.

In your region

Showing notes for

United States, Canada

This is called three-wire control: three wires connect the start button, the stop button and the holding contact of the starter. It gives low-voltage protection: after a power cut or an overload trip, the motor does not restart until someone presses start.

In two-wire control a maintained contact switches the coil directly. The motor stops when the power is lost, but it restarts on its own when the power returns if the contact is still closed.

Source: Siemens: Basics of Control Components, part 4 (STEP 2000 course)

UK & Ireland, Europe, Australia & New Zealand, Other IEC countries

No regional notes on this page yet. If something is different in your country, please send feedback.

Sources

  1. EEPower: Understanding three-wire control
  2. Fuji Electric: self-holding is released in a power cut (FER 56-3)
  3. Sprecher + Schuh: auxiliary contact terminal markings 13–14 and 21–22