A transmitter gives the measured value as a current of 4–20 mA. A two-wire transmitter takes its supply from the same loop it signals on, so it needs only two wires.
Wiring
- +24 V to the + terminal of the transmitter.
- From the − terminal of the transmitter to the PLC analogue input.
- From the analogue input to 0 V.
The current is the same at every point of the loop, so even a long cable does not change the signal, as long as the supply voltage is high enough. Use twisted, screened cable for analogue signals.
Scaling
value = start + (I − 4 mA) / 16 mA × (end − start)
Limit values can also be worked out in milliamperes: on a 0–4 m range, 3 m is 4 + 16 × 3 / 4 = 16 mA.
Fault limit
According to the NAMUR NE 43 recommendation, a current of 3.6 mA or less, or 21 mA or more, means a fault. The program checks the fault limit before it uses the value. Otherwise a broken wire looks like an empty tank or a low pressure.
Common mistakes
- The limit is calculated without the 4 mA start of the range. 3 m is not 15 mA but 16 mA.
- The transmitter is wired to a voltage input. For example, the analogue inputs of the LOGO! base module measure only 0–10 V, so a 4–20 mA transmitter needs a current input.
Sources
- Texas Instruments SLDA030: PGA900 as a two-wire 4–20 mA transmitter
- Vaisala PR-33-AC user guide: mA output fault level and NAMUR NE 43 ranges
- MicroControl: industrial standard signals, live zero and NE 43 ranges
- Siemens: LOGO! 8 manual (03/2019): wiring, operating modes, analogue inputs and technical data