Short explanations of control circuit terms. Each link takes you to the page where the topic is explained in more detail.
01Relay control
- Normally open contact (NO)
- A contact that is open at rest and closes when the device operates. On contactors and relays its terminal numbers end in 3 and 4, for example 13–14. Contactor →
- Normally closed contact (NC)
- A contact that is closed at rest and opens when the device operates. Its terminal numbers end in 1 and 2, for example 21–22. Contactor →
- Changeover contact
- A contact whose common terminal switches over from the NC side to the NO side, for example 15–16–18 on a timer relay. Auxiliary relay →
- Coil A1–A2
- The control terminals of a relay or contactor. When the coil is energised, the relay pulls in. Contactor →
- Self-holding (latching)
- The contactor's own NO contact in parallel with the start button keeps the contactor on after the button is released. Self-holding circuit →
- Interlocking
- NC contacts of two contactors, each in the coil circuit of the other, so that they cannot energise at the same time. Reversing and interlocking →
- On-delay
- The contact of a timer relay changes state only after the coil has been energised for the set time. Timer relay →
- Off-delay
- The contact of a timer relay returns only when the set time has elapsed after the control signal ended. Timer relay →
- Positive-opening contact
- An NC contact that the actuator forces apart mechanically. Even a contact that has welded shut is torn open. IEC 60947-5-1 calls this direct opening action. Emergency stop button →
- Reset
- A separate action that acknowledges a fault or emergency stop state before the next start. Emergency stop circuit →
- Control circuit and power circuit
- The control circuit controls relays and contactors. The power circuit carries the current of the load, for example a motor. Contactor →
- Utilisation category AC-3
- Contactor rating for starting squirrel-cage induction motors and switching them off while running. Contactor →
- Overload protection
- Protection that trips when the current is too high for too long. For example a thermal overload relay or the thermal trip of a motor protection circuit breaker. Thermal overload relay →
- Short-circuit protection
- Protection that breaks a short-circuit current at once. For example fuses or the magnetic trip of a motor protection circuit breaker. Switch-fuse →
- Trip class
- Tells how fast overload protection trips. A class 10 device trips from cold in 4–10 seconds at 7.2 times the set current. Thermal overload relay →
- Isolation
- Reliably disconnecting a circuit from the mains for maintenance work, for example with a local isolator. Local isolator →
- Star and delta
- The two ways of connecting the windings of a motor. In star the voltage across each winding is lower than in delta. Induction motor →
- Feedback loop
- An NC contact of a contactor in the reset circuit of a safety relay. A contactor that has welded shut prevents the reset. Safety relay →
- PNP sensor
- A three-wire sensor whose output switches the positive supply to the load: brown +, blue 0 V, black output. Sensors →
02Automation
- PLC (programmable logic controller)
- A device with push-buttons and sensors wired to its inputs, and contactors, indicator lights and valves to its outputs. The conditions that switch the outputs are written in the program. Small PLC →
- Input and output (I, Q)
- The connections of a PLC. Inputs I1, I2 … read push-buttons and sensors, outputs Q1, Q2 … control loads. Small PLC →
- Scan cycle
- The PLC reads all inputs, runs the program and writes the results to the outputs. The scan repeats continuously. Small PLC →
- Ladder diagram (LAD)
- A program drawn like a relay diagram turned on its side: contacts on the left, coil on the right. Small PLC →
- Memory bit (M)
- An internal auxiliary relay of the program, with no terminal. Small PLC →
- Relay output
- A PLC output that is the NO contact of a relay with its own terminals. It can switch a different voltage from the PLC supply. Small PLC →
- Transistor output
- A PLC output that gives the PLC's own 24 V to the load. The output current is small. Small PLC →
- RUN and STOP
- The operating modes of a PLC. In RUN mode the program is running. In STOP mode the inputs are not read and the relay outputs are open. Small PLC →
- 4–20 mA
- An analogue signal where the start of the measuring range is 4 mA and the end is 20 mA. Transmitter 4–20 mA →
- Two-wire (loop-powered) transmitter
- A transmitter that takes its supply from the same current loop it signals on. Transmitter to an analogue input →
- Live zero
- The measuring range starts at 4 mA and not at zero, so 0 mA means a fault, for example a broken wire. Transmitter 4–20 mA →
- Scaling
- Converting an analogue signal into a measured value. For example, on a 0–4 m range 12 mA is 2 m. Transmitter to an analogue input →
- NAMUR NE 43
- A recommendation that a current of 3.6 mA or less, or 21 mA or more, means a fault. Transmitter 4–20 mA →
- Ramp
- The drive raises or lowers the frequency steadily over a set time. Variable speed drive →
- Speed reference
- A voltage or current to the analogue input of the drive that sets the required speed. For example, 0–10 V is 0–50 Hz. Drive control with a PLC →
- 5/2 valve
- A solenoid valve with five ports and two positions. It is used to control a double-acting cylinder. Solenoid valve →
- Monostable and bistable
- A monostable valve returns to its rest position by spring when the coil is de-energised. A bistable valve stays in its position until the other coil is energised. Solenoid valve →
- Double-acting cylinder
- A pneumatic cylinder that compressed air moves in both directions. Pneumatic cylinder →
- Cylinder position sensor
- A sensor fixed to the side of a cylinder that detects the piston magnet and tells the PLC that the cylinder is at its end position. Cylinder control →
- Reed sensor
- A position sensor with a contact inside that the piston magnet closes. Pneumatic cylinder →