Glossary

Short explanations of control circuit terms. Each link takes you to the page where the topic is explained in more detail.

01Relay control

Normally open contact (NO)
A contact that is open at rest and closes when the device operates. On contactors and relays its terminal numbers end in 3 and 4, for example 13–14. Contactor →
Normally closed contact (NC)
A contact that is closed at rest and opens when the device operates. Its terminal numbers end in 1 and 2, for example 21–22. Contactor →
Changeover contact
A contact whose common terminal switches over from the NC side to the NO side, for example 15–16–18 on a timer relay. Auxiliary relay →
Coil A1–A2
The control terminals of a relay or contactor. When the coil is energised, the relay pulls in. Contactor →
Self-holding (latching)
The contactor's own NO contact in parallel with the start button keeps the contactor on after the button is released. Self-holding circuit →
Interlocking
NC contacts of two contactors, each in the coil circuit of the other, so that they cannot energise at the same time. Reversing and interlocking →
On-delay
The contact of a timer relay changes state only after the coil has been energised for the set time. Timer relay →
Off-delay
The contact of a timer relay returns only when the set time has elapsed after the control signal ended. Timer relay →
Positive-opening contact
An NC contact that the actuator forces apart mechanically. Even a contact that has welded shut is torn open. IEC 60947-5-1 calls this direct opening action. Emergency stop button →
Reset
A separate action that acknowledges a fault or emergency stop state before the next start. Emergency stop circuit →
Control circuit and power circuit
The control circuit controls relays and contactors. The power circuit carries the current of the load, for example a motor. Contactor →
Utilisation category AC-3
Contactor rating for starting squirrel-cage induction motors and switching them off while running. Contactor →
Overload protection
Protection that trips when the current is too high for too long. For example a thermal overload relay or the thermal trip of a motor protection circuit breaker. Thermal overload relay →
Short-circuit protection
Protection that breaks a short-circuit current at once. For example fuses or the magnetic trip of a motor protection circuit breaker. Switch-fuse →
Trip class
Tells how fast overload protection trips. A class 10 device trips from cold in 4–10 seconds at 7.2 times the set current. Thermal overload relay →
Isolation
Reliably disconnecting a circuit from the mains for maintenance work, for example with a local isolator. Local isolator →
Star and delta
The two ways of connecting the windings of a motor. In star the voltage across each winding is lower than in delta. Induction motor →
Feedback loop
An NC contact of a contactor in the reset circuit of a safety relay. A contactor that has welded shut prevents the reset. Safety relay →
PNP sensor
A three-wire sensor whose output switches the positive supply to the load: brown +, blue 0 V, black output. Sensors →

02Automation

PLC (programmable logic controller)
A device with push-buttons and sensors wired to its inputs, and contactors, indicator lights and valves to its outputs. The conditions that switch the outputs are written in the program. Small PLC →
Input and output (I, Q)
The connections of a PLC. Inputs I1, I2 … read push-buttons and sensors, outputs Q1, Q2 … control loads. Small PLC →
Scan cycle
The PLC reads all inputs, runs the program and writes the results to the outputs. The scan repeats continuously. Small PLC →
Ladder diagram (LAD)
A program drawn like a relay diagram turned on its side: contacts on the left, coil on the right. Small PLC →
Memory bit (M)
An internal auxiliary relay of the program, with no terminal. Small PLC →
Relay output
A PLC output that is the NO contact of a relay with its own terminals. It can switch a different voltage from the PLC supply. Small PLC →
Transistor output
A PLC output that gives the PLC's own 24 V to the load. The output current is small. Small PLC →
RUN and STOP
The operating modes of a PLC. In RUN mode the program is running. In STOP mode the inputs are not read and the relay outputs are open. Small PLC →
4–20 mA
An analogue signal where the start of the measuring range is 4 mA and the end is 20 mA. Transmitter 4–20 mA →
Two-wire (loop-powered) transmitter
A transmitter that takes its supply from the same current loop it signals on. Transmitter to an analogue input →
Live zero
The measuring range starts at 4 mA and not at zero, so 0 mA means a fault, for example a broken wire. Transmitter 4–20 mA →
Scaling
Converting an analogue signal into a measured value. For example, on a 0–4 m range 12 mA is 2 m. Transmitter to an analogue input →
NAMUR NE 43
A recommendation that a current of 3.6 mA or less, or 21 mA or more, means a fault. Transmitter 4–20 mA →
Ramp
The drive raises or lowers the frequency steadily over a set time. Variable speed drive →
Speed reference
A voltage or current to the analogue input of the drive that sets the required speed. For example, 0–10 V is 0–50 Hz. Drive control with a PLC →
5/2 valve
A solenoid valve with five ports and two positions. It is used to control a double-acting cylinder. Solenoid valve →
Monostable and bistable
A monostable valve returns to its rest position by spring when the coil is de-energised. A bistable valve stays in its position until the other coil is energised. Solenoid valve →
Double-acting cylinder
A pneumatic cylinder that compressed air moves in both directions. Pneumatic cylinder →
Cylinder position sensor
A sensor fixed to the side of a cylinder that detects the piston magnet and tells the PLC that the cylinder is at its end position. Cylinder control →
Reed sensor
A position sensor with a contact inside that the piston magnet closes. Pneumatic cylinder →